Quick Answer
Record the ADA door opening force at handover with a pressure gauge after the closer is finally adjusted. Retract the latch, place the gauge about 2.5 inches from the latch edge and just above the hardware, then push perpendicular to the door through a slow swing to 70 degrees. Enter the reading, limit, tested side, closer setting and pass/fail status in the door log. OUBAO’s T90 offers valve-adjustable power #2–#4 for a defined starting point.
Why Is a Field Reading Different From a Factory Setting?
A factory setting is only a starting point. Field handover is the point when the completed door is accepted by the owner or main contractor, and the reading then reflects the final door weight, width, seals, hinges, frame alignment, air pressure and closer setting.
Those conditions change the force a user must apply. A closer adjusted on a bench or delivered at a nominal power size can read differently once the door is hung, the weatherstripping is fitted and the latch is released. The handover test proves the installed condition, not the catalogue description.
Record the result only after final adjustment. If a technician changes the closer setting, moves the arm or replaces a seal after the test, repeat the measurement and update the record. The door closer adjustment steps show the sequence for sweep and latch settings before the final check.
What Does ADA Require for Door Opening Force?
For a project covered by the 2010 ADA Standards, Section 404.2.9 sets the ADA door opening force limit at 5 pounds of force (22.2 N) for interior hinged doors and for sliding or folding doors. Fire doors instead use the minimum opening force allowed by the authority having jurisdiction. Exterior hinged doors have no ADA maximum, although a local code or project specification may set one.
The limit applies to the continuous force needed to open the door fully, not the first pull that breaks a seal. Retract the latch and release any other device that holds the door closed before measuring. Latch and hardware operation are checked separately, so do not include that resistance in the ADA door opening force reading.
Test the side and direction used on the accessible route. Where a door is usable in both directions, check both. Local accessibility rules, client standards or a stricter project specification can override the federal minimum, so confirm the governing limit before the first test.
How Do You Measure ADA Door Opening Force at Handover?
Use a door pressure gauge and the same ADA door opening force test sequence on every door:
- Open the door so the face edge aligns with the outside edge of the frame.
- Place the gauge immediately above the door hardware, about 2.5 inches from the latch edge.
- Push slowly, keeping the gauge perpendicular to the door face.
- Remove the gauge when the door reaches 70 degrees.
- Repeat the test and record the result.
Follow the gauge manufacturer’s instructions where they differ. A gauge in poor condition, a hurried push or a gauge held at an angle can make a compliant door look heavy or a heavy door look acceptable.
Reading the Gauge
Record the continuous force shown during the controlled swing, not the initial tug needed to break the seal or retract the latch. Keep the unit used by the project specification, normally pounds of force, and add newtons in brackets where both are useful.
If two readings differ, repeat the test and investigate the cause before entering a final value. A single number without the test side, direction and closer setting is difficult to defend at acceptance.
Conditions to Record
Record whether the door is interior or exterior, hinged, sliding or folding, and fire-rated or non-fire-rated. Note the door leaf width and weight, closer model and mounting, arm type, power setting and whether the latch was retracted. Also note any unusual stack pressure, wind or seal drag present during the test.

Build a Door Log That Survives Handover
Use one row per door and keep the supporting photos with the same door ID. A useful ADA door opening force record contains:
- Door ID, location and floor.
- Door type, leaf width, leaf weight and fire rating.
- Closer model, mounting method and power setting.
- Test side, direction and whether the latch was retracted.
- Gauge ID, calibration status, tester and date.
- Measured force, governing limit and pass/fail result.
- Corrective action, retest value and acceptance signature.
Keep closing speed in a separate field. The ADA door opening force result should stand alone, because a door can pass this check and still close too quickly. Photos of the closer label, arm and gauge display make later service and replacement easier.
How Should a Failed Reading Be Handled?
Do not sign off a failed door and do not hide the first reading. Confirm that the latch is fully retracted, the gauge is square to the door and the test follows the same starting position. Then check closer power, door binding, hinge alignment, seal drag and stack pressure.
Adjust the closer within its approved range and repeat the full measurement. On a fire door, keep the model, mounting and adjustment within the tested assembly and the authority’s requirements. The fire-rated door closer selection guide explains why the complete assembly matters. If the door still fails, record the original value, the action taken and the unresolved cause rather than averaging the results.

Choose a Closer That Can Be Verified
An adjustable closer with a clear power setting makes handover easier. The installer can set a defined starting point, measure the result and correct it without changing the whole unit. Stable adjustment also helps a distributor support different door weights from one stock line.
OUBAO’s T90/T30 cam door closer uses slide-arm mounting and adjustable closing and latching speed. T90 sets power #2, #3 or #4 with a valve; T30 sets #3 or #4 by position. Both are non-handed, and the cam-action design is intended for light opening operation. The installed ADA door opening force reading remains the acceptance result.
- Yes, this series can be equipped with a hold-open arm to realize the hold-open function. This series is designed for various door types, including wooden and metal doors.

The 5000 Series classic closer is another adjustable-power option with standard backcheck; delayed action is optional. For other mounting arrangements, compare the door closer collection or the broader door closer range.
- This series is designed for various door types, including wooden and metal doors. Yes, this series features a non-handed design.

What Should Buyers Send With the Enquiry?
Send the door type, door weight and width, mounting method, target market, required documents and quantity. Add the project’s ADA door opening force limit, fire rating, required closing functions and any local accessibility standard. That lets OUBAO confirm the closer model, power range, mounting configuration and document set before quotation.
Do not rely on a generic “ADA compliant” request. State the door and the test limit so the supplier can match the hardware to the actual opening. A clear brief also tells the installer what reading must appear in the handover log.
Conclusion
Record ADA door opening force after the door is complete and the closer is finally adjusted. Use the same gauge position and slow swing on every leaf, record the side and setting with the number, and retest after any change. A clean log protects the installer, gives the owner a service baseline and shows whether the closer was specified correctly.