Quick Answer
An access control battery backup for maglock is a separate power supply, charger and battery set that keeps the lock circuit energized during an outage. Specify it in this order: confirm when the door must lock or release, list every backed-up load, calculate current at the actual voltage, set the runtime, then choose a power supply with the charger, monitoring and release inputs the project needs. OUBAO’s OB280 and CK280 are two 280 kg starting points; size from the exact model datasheet.
What Does Access Control Battery Backup Mean for a Maglock?
A maglock is normally a fail-safe device: it locks while energized and releases when its power is removed. An access control battery backup does not change that principle. It is a power supply with a charger and batteries upstream of the lock, keeping the lock circuit energized when mains power fails.
That distinction matters for buyers. A battery inside the lock is not the normal arrangement. The backup is part of the access-control power design, and its behavior must be coordinated with the controller, exit devices and fire-alarm interface. Buyers often call this a maglock battery backup, but the battery belongs to the power supply, not the lock.
What Release Logic Should You Set Before Capacity?
Decide what the door must do during a normal outage, a fire alarm and an emergency release before anyone calculates battery size. An access control battery backup can keep a maglock locked during a utility failure, but it must not prevent the lock from releasing when the fire-alarm or emergency circuit removes power.
Write the sequence into the specification: normal operation, power failure, fire alarm, manual release and restoration. If the project requires the door to unlock whenever normal power is lost, a battery backup may not be appropriate for that opening. If the project requires the door to stay secure for a defined period, confirm that the local authority and the door’s exit strategy allow it. The fail-safe and fail-secure lock guide explains the difference in plain terms.
Build a Door-by-Door Load Schedule
Start the access control battery backup schedule by listing every device the standby supply will carry, door by door. The largest continuous load is usually the maglock, but the controller, reader, request-to-exit sensor, door position switch, network module, sounder or other accessories may also be connected. Include only the loads assigned to the backed-up supply, and note which are continuous, standby or intermittent.
| Load | When it draws current | Data to record |
|---|---|---|
| Maglock | Continuously while locked | Exact model, voltage and operating current |
| Controller and reader | Standby and active states | Supply voltage, standby current and peak current |
| Release and monitoring devices | Alarm or request-to-exit event | Voltage, current and whether they remain powered |
| Accessories | As installed | Datasheet current and duty |
Use the current stated for the actual voltage. The OB280 and CK280 Series both list 12 V DC, with 24 V DC available on request, but the exact current draw must come from the selected submodel’s datasheet. A holding-force rating is not a battery load.

How Do You Size Access Control Battery Backup Capacity?
Size the access control battery backup from the approved load schedule and the required runtime, not from the door’s holding force. For a simple DC load, multiply total current by backup hours to get ampere-hours at the same voltage:
Backup load (Ah) = total current (A) × required runtime (h)
That figure is only the starting point. The battery’s usable capacity depends on its discharge rate, end voltage, temperature and age, so apply the battery manufacturer’s derating and the project’s design margin. Also confirm that the power supply can carry the operating load and recharge the battery within the required recovery time.
For illustration only, a 1.5 A load for four hours gives 6 Ah before derating. The final battery must be larger than that figure. Do not size a maglock battery backup at 100% depth of discharge or assume that a higher holding-force model draws the same current as a lower one. The exact model data and power-supply instructions decide.

Specify the Power Supply and Charger
The access control battery backup should match the lock voltage, the calculated load and the battery type selected for the project. Put the required output voltage and continuous current on the schedule, then add the charger rating, battery capacity and recharge time.
Include these specification items:
- A charger designed for the selected battery chemistry and capacity.
- AC-fail, low-battery, battery-fault and output-protection monitoring where the project requires them.
- Individual fused or breaker-protected outputs if one supply serves several doors.
- A fire-alarm release input that removes power from the maglock circuit even while the battery is connected.
- An enclosure with space for the batteries, lockable access, ventilation and the environmental rating the location needs.
- The operating temperature range and any battery placement limit.
A cleaner specification separates normal lock power from the emergency release function. The backup keeps the security circuit running; the alarm interface must be able to override it. That is the difference between a useful battery system and one that traps the release circuit.
How Do Cable Runs Affect Lock Voltage?
The access control battery backup must deliver its rated voltage at the lock, not only at the supply terminals. Check the voltage under full load. Long cable runs, undersized conductors and shared circuits can reduce the voltage delivered to the maglock. A lock that receives less than its rated voltage may not hold its stated force, and a battery that is near the end of its runtime may make the problem worse.
Record the distance from the supply to each door, the conductor size and the intended load. Use the power-supply or lock manufacturer’s wiring guidance to select the conductor and keep voltage drop within the allowed range. The magnetic lock wiring diagram guide is a useful starting point for the circuit layout. If the supply is far from the doors, a local power supply or a larger conductor may be more practical than one central unit.
Which OUBAO Maglock Fits the Load Schedule?
Choose the lock and mounting variant first, then use its exact electrical data in the load schedule. OUBAO’s OB280 Series is the regular commercial 280 kg (600 lb) nominal series. The CK280 Series is the cost-oriented 280 kg (600 lb) series. Both list 12 V DC, with 24 V DC available on request.
The two series should be compared as separate product lines, not as one series with a different label. The OB280 and CK280 offer several submodels, so confirm the mounting arrangement, monitoring option and voltage for the exact model before finalizing the battery load. If the project needs a different holding-force class, compare the wider magnetic lock range and keep the same electrical discipline.
- Commercial Buildings : Offices, shopping malls, hotels, restaurants and retail stores Public Facilities : Hospitals, schools, airports, libraries and government buildings

Handover Tests for the Backed-Up Circuit
Test the access control battery backup as a system and record the result. With normal power connected, confirm the charger is operating, the battery is charged and the lock is secure. Then simulate a mains failure and measure the voltage at each lock, the total current and the time the system remains within its operating range.
Test the fire-alarm release separately. The lock must release when the alarm interface operates, even though the battery is connected, and it must remain released until the system is reset. Check that the monitoring signals report AC failure, low battery and any output fault. After power is restored, confirm the battery recharges and the lock returns to normal operation.
Keep a handover record with the battery model, capacity, installation date, load schedule, measured runtime and test result. That record lets the facility team repeat the test and replace the battery before performance drops.
Conclusion
Access control battery backup is a power-design decision, not a lock accessory. Set the release logic first, build a door-by-door load schedule, size the battery from measured current and required runtime, and verify voltage at the lock. Then test the backed-up circuit and the fire-alarm release as separate functions. OUBAO can help match the OB280 or CK280 to your opening and OEM/ODM requirements.
Share the door type, door weight and width, mounting method, target market, required documents and quantity with OUBAO so the team can confirm the lock configuration and prepare a model-specific quotation.



